Rule Fire protection directive 16-15 Escape and rescue routes
Atria and inner courtyards: escape routes only with smoke and heat exhaust, verified
VKF-16-15-030
pragmaticBIM.ch/vkf-16-15-030
Escape routes across atria and inner courtyards are allowed if smoke and heat exhaust systems ensure safe walkability, shown by a verification. For further fire protection requirements for buildings with atria, the appendix refers to the VKF fire protection explanation on buildings with atria and inner courtyards.
Description
Not yet checkable: smoke and heat exhaust and the verification are not represented in the model.
Source
VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 13)
More rules for Fire protection directive 16-15 Escape and rescue routes
-
VKF-16-15-001
Escape route to an exit or stair at most 50 m
From no point of an interior space may the route to the nearest exit to the outside or the nearest stair (vertical escape route) exceed 50 m. The 50 m apply only where two separate exits or stairs can be reached; otherwise the 35 m limit applies (VKF-16-15-002).
-
VKF-16-15-002
Escape route with a single exit at most 35 m
Where only one exit to the outside or only one stair serves as vertical escape route, the route from the most remote point of an interior space is limited to 35 m. The model does not show whether a second, independent escape route exists, so the check reports routes above 35 m as a warning.
-
VKF-16-15-003
Doors on escape routes: clear width at least 0.90 m
A door that an escape route passes through needs a clear opening width of at least 0.90 m. Depending on the use, smaller sizes are allowed, for example for doors to ancillary or small rooms.