Rule Fire protection directive 16-15 Escape and rescue routes
High-rise buildings: safety stairwells with airlocks
VKF-16-15-029
pragmaticBIM.ch/vkf-16-15-029
In high-rise buildings, storeys above ground are served by safety stairwells. These are vertical escape routes specially protected against the entry of smoke and fire (pressurized smoke control system).
Description
The roof must be accessible from a safety stairwell. Internal safety stairwells are entered on every storey through an airlock directly in front with a plan size of at least 1.2 m × 2.4 m, whose doors are self-closing. No airlock is needed where access is through forecourts or corridors permanently open to the outside. With a firefighters' lift, the airlock or forecourt in front of it must, according to the appendix, measure at least 2.4 m × 2.4 m. Not yet checkable: high-rise status, pressurization system and airlock dimensions are missing in the model.
Source
VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 13)
More rules for Fire protection directive 16-15 Escape and rescue routes
-
VKF-16-15-001
Escape route to an exit or stair at most 50 m
From no point of an interior space may the route to the nearest exit to the outside or the nearest stair (vertical escape route) exceed 50 m. The 50 m apply only where two separate exits or stairs can be reached; otherwise the 35 m limit applies (VKF-16-15-002).
-
VKF-16-15-002
Escape route with a single exit at most 35 m
Where only one exit to the outside or only one stair serves as vertical escape route, the route from the most remote point of an interior space is limited to 35 m. The model does not show whether a second, independent escape route exists, so the check reports routes above 35 m as a warning.
-
VKF-16-15-030
Atria and inner courtyards: escape routes only with smoke and heat exhaust, verified
Escape routes across atria and inner courtyards are allowed if smoke and heat exhaust systems ensure safe walkability, shown by a verification. For further fire protection requirements for buildings with atria, the appendix refers to the VKF fire protection explanation on buildings with atria and inner courtyards.