Rule Fire protection directive 16-15 Escape and rescue routes

Accommodation: horizontal evacuation, hotel room doors, reception

VKF-16-15-026 pragmaticBIM.ch/vkf-16-15-026

On bed floors of accommodation [a] where sick, care-dependent or assistance-dependent people are housed, the horizontal escape routes are subdivided so that, together with the patient rooms, at least two independent fire compartments allow horizontal evacuation.

Description

Reception offices separated with EI 60 need only EI 30 towards vertical escape routes and an RF1 separation towards horizontal ones; doors get self-closers. Rooms may be combined into one unit if the escape routes lead through a shared anteroom and measure at most 20 m to a horizontal or vertical escape route. In accommodation [b] and [c], reception counters separated with EI 30 may stand in horizontal rescue routes. Hotel room doors are at least 0.8 m wide and need not open in the escape direction; doors within hotel suites have no requirements. In [c], building entrance doors need not open in the escape direction, and winding stairs 1.2 m wide with an inner tread width of at least 0.1 m are allowed. Not yet checkable: accommodation class, fire compartments and door swing are often missing in the model.

Source

VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 12)