Rule Fire protection directive 16-15 Escape and rescue routes
Accommodation: horizontal evacuation, hotel room doors, reception
VKF-16-15-026
pragmaticBIM.ch/vkf-16-15-026
On bed floors of accommodation [a] where sick, care-dependent or assistance-dependent people are housed, the horizontal escape routes are subdivided so that, together with the patient rooms, at least two independent fire compartments allow horizontal evacuation.
Description
Reception offices separated with EI 60 need only EI 30 towards vertical escape routes and an RF1 separation towards horizontal ones; doors get self-closers. Rooms may be combined into one unit if the escape routes lead through a shared anteroom and measure at most 20 m to a horizontal or vertical escape route. In accommodation [b] and [c], reception counters separated with EI 30 may stand in horizontal rescue routes. Hotel room doors are at least 0.8 m wide and need not open in the escape direction; doors within hotel suites have no requirements. In [c], building entrance doors need not open in the escape direction, and winding stairs 1.2 m wide with an inner tread width of at least 0.1 m are allowed. Not yet checkable: accommodation class, fire compartments and door swing are often missing in the model.
Source
VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 12)
More rules for Fire protection directive 16-15 Escape and rescue routes
-
VKF-16-15-027
Car parks: airlocks or forecourts for compartments above 1200 m²
If exits of a parking area lead into a vertical escape route and the fire compartment area exceeds 1200 m², fire-resistant airlocks or forecourts are to be provided. The fire resistance of the airlocks matches that of the load-bearing structure but is at least EI 30.
-
VKF-16-15-028
Agriculture: two exits for stables above 200 m²
Stables with a floor area above 200 m² need at least two suitably placed, sufficiently large exits through which livestock can also be evacuated. The doors open in the escape direction.
-
VKF-16-15-029
High-rise buildings: safety stairwells with airlocks
In high-rise buildings, storeys above ground are served by safety stairwells. These are vertical escape routes specially protected against the entry of smoke and fire (pressurized smoke control system).