Rule Fire protection directive 16-15 Escape and rescue routes
Car parks: airlocks or forecourts for compartments above 1200 m²
VKF-16-15-027
pragmaticBIM.ch/vkf-16-15-027
If exits of a parking area lead into a vertical escape route and the fire compartment area exceeds 1200 m², fire-resistant airlocks or forecourts are to be provided. The fire resistance of the airlocks matches that of the load-bearing structure but is at least EI 30.
Description
The airlock doors to the vertical or horizontal escape route are to be self-closing with E 30. The appendix notes that locked accesses from car parks to vertical escape routes (e.g. in residential buildings) do not count as escape routes. Not yet checkable: fire compartment areas and airlocks are not identified in the model.
Source
VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 12)
More rules for Fire protection directive 16-15 Escape and rescue routes
-
VKF-16-15-028
Agriculture: two exits for stables above 200 m²
Stables with a floor area above 200 m² need at least two suitably placed, sufficiently large exits through which livestock can also be evacuated. The doors open in the escape direction.
-
VKF-16-15-029
High-rise buildings: safety stairwells with airlocks
In high-rise buildings, storeys above ground are served by safety stairwells. These are vertical escape routes specially protected against the entry of smoke and fire (pressurized smoke control system).
-
VKF-16-15-030
Atria and inner courtyards: escape routes only with smoke and heat exhaust, verified
Escape routes across atria and inner courtyards are allowed if smoke and heat exhaust systems ensure safe walkability, shown by a verification. For further fire protection requirements for buildings with atria, the appendix refers to the VKF fire protection explanation on buildings with atria and inner courtyards.