Rule Fire protection directive 16-15 Escape and rescue routes

Shops: circulation routes 1.2 m, main routes 1.8 m, escape streets 3.6 m

VKF-16-15-024 pragmaticBIM.ch/vkf-16-15-024

Shops must have circulation routes serving escape; where they merge, main circulation routes arise. Circulation routes are at least 1.2 m wide and main routes at least 1.8 m.

Description

Where several main routes merge, escape streets at least 3.6 m wide are needed, with exits at both ends leading directly outside and having the same door width as the street. The distance within the escape street is not counted towards the total escape route length. If a room has only one escape route opening onto the escape street, the escape route within the use unit is limited to 20 m. Not yet checkable: circulation routes, main routes and escape streets are not identified as such in the model.

Source

VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 11)