Rule Fire protection directive 16-15 Escape and rescue routes
Shops: circulation routes 1.2 m, main routes 1.8 m, escape streets 3.6 m
VKF-16-15-024
pragmaticBIM.ch/vkf-16-15-024
Shops must have circulation routes serving escape; where they merge, main circulation routes arise. Circulation routes are at least 1.2 m wide and main routes at least 1.8 m.
Description
Where several main routes merge, escape streets at least 3.6 m wide are needed, with exits at both ends leading directly outside and having the same door width as the street. The distance within the escape street is not counted towards the total escape route length. If a room has only one escape route opening onto the escape street, the escape route within the use unit is limited to 20 m. Not yet checkable: circulation routes, main routes and escape streets are not identified as such in the model.
Source
VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 11)
More rules for Fire protection directive 16-15 Escape and rescue routes
-
VKF-16-15-025
Seating: passage 0.45 m, at most 32 or 16 seats per row
In rooms with large occupancy, seats are arranged in rows and interrupted by aisles so that the exits can be reached as directly as possible. The free passage between rows is at least 0.45 m, and circulation routes are at least 1.2 m wide.
-
VKF-16-15-026
Accommodation: horizontal evacuation, hotel room doors, reception
On bed floors of accommodation [a] where sick, care-dependent or assistance-dependent people are housed, the horizontal escape routes are subdivided so that, together with the patient rooms, at least two independent fire compartments allow horizontal evacuation.
-
VKF-16-15-027
Car parks: airlocks or forecourts for compartments above 1200 m²
If exits of a parking area lead into a vertical escape route and the fire compartment area exceeds 1200 m², fire-resistant airlocks or forecourts are to be provided. The fire resistance of the airlocks matches that of the load-bearing structure but is at least EI 30.