Rule Fire protection directive 16-15 Escape and rescue routes

Seating: passage 0.45 m, at most 32 or 16 seats per row

VKF-16-15-025 pragmaticBIM.ch/vkf-16-15-025

In rooms with large occupancy, seats are arranged in rows and interrupted by aisles so that the exits can be reached as directly as possible. The free passage between rows is at least 0.45 m, and circulation routes are at least 1.2 m wide.

Description

A row accessible from two sides has at most 32 seats, a row accessible from one side only at most 16. Seating is fixed to the floor where possible; otherwise the chairs of a row are linked so the audience cannot detach them. Chairs in circulation routes are prohibited, and folding seats along circulation routes fold up automatically. Not yet checkable: seat rows and seat counts are not stored in a structured way in the model.

Source

VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 11)