Rule Fire protection directive 16-15 Escape and rescue routes
Seating: passage 0.45 m, at most 32 or 16 seats per row
VKF-16-15-025
pragmaticBIM.ch/vkf-16-15-025
In rooms with large occupancy, seats are arranged in rows and interrupted by aisles so that the exits can be reached as directly as possible. The free passage between rows is at least 0.45 m, and circulation routes are at least 1.2 m wide.
Description
A row accessible from two sides has at most 32 seats, a row accessible from one side only at most 16. Seating is fixed to the floor where possible; otherwise the chairs of a row are linked so the audience cannot detach them. Chairs in circulation routes are prohibited, and folding seats along circulation routes fold up automatically. Not yet checkable: seat rows and seat counts are not stored in a structured way in the model.
Source
VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 11)
More rules for Fire protection directive 16-15 Escape and rescue routes
-
VKF-16-15-026
Accommodation: horizontal evacuation, hotel room doors, reception
On bed floors of accommodation [a] where sick, care-dependent or assistance-dependent people are housed, the horizontal escape routes are subdivided so that, together with the patient rooms, at least two independent fire compartments allow horizontal evacuation.
-
VKF-16-15-027
Car parks: airlocks or forecourts for compartments above 1200 m²
If exits of a parking area lead into a vertical escape route and the fire compartment area exceeds 1200 m², fire-resistant airlocks or forecourts are to be provided. The fire resistance of the airlocks matches that of the load-bearing structure but is at least EI 30.
-
VKF-16-15-028
Agriculture: two exits for stables above 200 m²
Stables with a floor area above 200 m² need at least two suitably placed, sufficiently large exits through which livestock can also be evacuated. The doors open in the escape direction.