Rule Fire protection directive 16-15 Escape and rescue routes

Housing: relaxations for separations, stairs and doors

VKF-16-15-019 pragmaticBIM.ch/vkf-16-15-019

In residential buildings of low and medium height, fire separations between horizontal and vertical escape routes may be omitted if the floor area per vertical escape route is at most 900 m², the horizontal escape routes between vertical ones are subdivided with fire resistance, and they match the vertical ones in...

Description

In residential buildings of low and medium height, fire separations between horizontal and vertical escape routes may be omitted if the floor area per vertical escape route is at most 900 m², the horizontal escape routes between vertical ones are subdivided with fire resistance, and they match the vertical ones in material, fire resistance and risk of activation. For low buildings, winding stairs 1.2 m wide with an inner tread width of at least 0.1 m are allowed. If a stair serves at most one upper and one lower storey, straight stairs of 0.9 m suffice. Within the dwelling there are no stair requirements, and doors inside the dwelling are exempt from the width and swing rules. Dwelling entrance doors need not open in the escape direction; building entrance doors need not either if they serve at most 10 dwellings. The escape route may lead through several rooms within the use unit. Not yet checkable: building height class, dwelling units and fire separations are often missing in the model.

Source

VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 9)