Rule Fire protection directive 16-15 Escape and rescue routes

Office, trade and industry: relaxations and door dimensions

VKF-16-15-020 pragmaticBIM.ch/vkf-16-15-020

In office buildings of low height, fire separations between horizontal and vertical escape routes may be omitted if the floor area per vertical escape route is at most 900 m², the horizontal escape routes are subdivided with fire resistance and match the vertical ones in material, fire resistance and risk of...

Description

In office buildings of low height, fire separations between horizontal and vertical escape routes may be omitted if the floor area per vertical escape route is at most 900 m², the horizontal escape routes are subdivided with fire resistance and match the vertical ones in material, fire resistance and risk of activation. Winding stairs 1.2 m wide with an inner tread width of at least 0.1 m are allowed for low buildings; within the use unit there are no stair requirements. For doors, businesses subject to Ordinance 4 to the Labour Act follow that ordinance. For businesses not subject to it, the clear passage of doors to rooms for at most 20 people may drop to 0.8 m; up to 6 people, sliding doors are possible. The escape route within the use unit may lead through at most one adjoining room. Not yet checkable: building height, subjection to ArGV 4 and occupancy are missing in the model.

Source

VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 9)

More rules for Fire protection directive 16-15 Escape and rescue routes