Rule Fire protection directive 16-15 Escape and rescue routes

Schools and day-care centres: relaxations and short routes

VKF-16-15-021 pragmaticBIM.ch/vkf-16-15-021

In school buildings of low height, fire separations between horizontal and vertical escape routes may be omitted if the floor area per vertical escape route is at most 900 m², the horizontal escape routes are subdivided with fire resistance and match the vertical ones in material, fire resistance and risk of...

Description

In school buildings of low height, fire separations between horizontal and vertical escape routes may be omitted if the floor area per vertical escape route is at most 900 m², the horizontal escape routes are subdivided with fire resistance and match the vertical ones in material, fire resistance and risk of activation; open cloakrooms with hooks and fixed benches are excepted. Within the use unit there are no stair requirements. The escape route within the storey or use unit may lead through at most one adjoining room (e.g. classroom, group room, gymnasium, cloakroom). In day-care centres, escape routes through rooms of the use unit are at most 20 m long, doors within the use unit are exempt from the width and swing rules, and sleeping rooms on mezzanines or galleries are served by horizontal and vertical escape routes. Not yet checkable: school use, building height and fire separations are often missing in the model.

Source

VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 10)