Rule Fire protection directive 16-15 Escape and rescue routes
Stairs and ramps with large occupancy: width, steps, gradient
VKF-16-15-022
pragmaticBIM.ch/vkf-16-15-022
For shops and rooms with large occupancy, the total width of stair flights and landings follows the widest exit of the connected storeys. Stairs wider than 2.4 m are divided by handrails.
Description
On horizontal escape routes single steps are not allowed; a sequence of at least three steps is permitted if clearly marked. Ramps on escape routes have a gradient of at most 6 %. Not yet checkable: stair width, exit widths and ramp gradient are not consistently typed in the model.
Source
VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 11)
More rules for Fire protection directive 16-15 Escape and rescue routes
-
VKF-16-15-023
Record occupancy, room exits directly onto escape routes
The decisive occupancy determines the number and dimensions of escape routes and is to be recorded in writing and bindingly. Where no binding data exist (e.g. seating plans), area-based assumptions apply and may be adapted to the project.
-
VKF-16-15-024
Shops: circulation routes 1.2 m, main routes 1.8 m, escape streets 3.6 m
Shops must have circulation routes serving escape; where they merge, main circulation routes arise. Circulation routes are at least 1.2 m wide and main routes at least 1.8 m.
-
VKF-16-15-025
Seating: passage 0.45 m, at most 32 or 16 seats per row
In rooms with large occupancy, seats are arranged in rows and interrupted by aisles so that the exits can be reached as directly as possible. The free passage between rows is at least 0.45 m, and circulation routes are at least 1.2 m wide.