Rule Fire protection directive 16-15 Escape and rescue routes

Stairs and ramps with large occupancy: width, steps, gradient

VKF-16-15-022 pragmaticBIM.ch/vkf-16-15-022

For shops and rooms with large occupancy, the total width of stair flights and landings follows the widest exit of the connected storeys. Stairs wider than 2.4 m are divided by handrails.

Description

On horizontal escape routes single steps are not allowed; a sequence of at least three steps is permitted if clearly marked. Ramps on escape routes have a gradient of at most 6 %. Not yet checkable: stair width, exit widths and ramp gradient are not consistently typed in the model.

Source

VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 11)

More rules for Fire protection directive 16-15 Escape and rescue routes