Rule Fire protection directive 16-15 Escape and rescue routes
Horizontal escape routes: lead to the vertical route, subdivided above 50 m
VKF-16-15-015
pragmaticBIM.ch/vkf-16-15-015
Horizontal escape routes lead to a vertical escape route or to a safe place outside. If they are longer than 50 m, fire separations divide them so that escape routes of similar length result.
Description
Built-in cupboards are allowed if their surfaces facing the escape route consist of RF1 materials. Where there is no fire separation between the horizontal and the vertical escape route, the horizontal route must meet the same requirements as the vertical one. Not yet checkable: fire separations and the reaction to fire of surfaces are not consistently given in the model.
Source
VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 7)
More rules for Fire protection directive 16-15 Escape and rescue routes
-
VKF-16-15-016
Access balconies: open, made of RF1, leading to the vertical escape route
Access balconies lead to vertical escape routes and consist of RF1 materials; linear load-bearing members may be combustible. They are permanently open to the outside for at least half, with evenly distributed openings that cannot be closed.
-
VKF-16-15-017
Doors on rescue routes openable from outside, automatic doors suitable
Doors on rescue routes must be openable from outside by the emergency services. Automatic sliding and revolving doors are allowed on escape routes if they ensure escape at all times and are suitable for this use.
-
VKF-16-15-018
Buildings with small dimensions: 35 m escape route, narrower stairs
In buildings with small dimensions the escape route to a safe place outside is at most 35 m and may lead through several rooms within the use unit.