Rule Fire protection directive 16-15 Escape and rescue routes
Doors on rescue routes openable from outside, automatic doors suitable
VKF-16-15-017
pragmaticBIM.ch/vkf-16-15-017
Doors on rescue routes must be openable from outside by the emergency services. Automatic sliding and revolving doors are allowed on escape routes if they ensure escape at all times and are suitable for this use.
Description
For high-speed doors it is enough if they can be opened quickly and safely by hand in the escape direction without aids. For locked escape doors the appendix normally refers to emergency exit or panic exit devices under SN EN 179 or SN EN 1125. Not yet checkable: drive type and hardware of doors are not typed in the model.
Source
VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 8)
More rules for Fire protection directive 16-15 Escape and rescue routes
-
VKF-16-15-018
Buildings with small dimensions: 35 m escape route, narrower stairs
In buildings with small dimensions the escape route to a safe place outside is at most 35 m and may lead through several rooms within the use unit.
-
VKF-16-15-019
Housing: relaxations for separations, stairs and doors
In residential buildings of low and medium height, fire separations between horizontal and vertical escape routes may be omitted if the floor area per vertical escape route is at most 900 m², the horizontal escape routes between vertical ones are subdivided with fire resistance, and they match the vertical ones in...
-
VKF-16-15-020
Office, trade and industry: relaxations and door dimensions
In office buildings of low height, fire separations between horizontal and vertical escape routes may be omitted if the floor area per vertical escape route is at most 900 m², the horizontal escape routes are subdivided with fire resistance and match the vertical ones in material, fire resistance and risk of...