Rule Fire protection directive 16-15 Escape and rescue routes
Exit width above 200 people: 0.6 m per 100 or per 60 people
VKF-16-15-013
pragmaticBIM.ch/vkf-16-15-013
With an occupancy above 200 people, the exits together must be at least 0.6 m wide per 100 people where the route leads outside at ground level, and at least 0.6 m per 60 people where it leads over stairs. Example from the appendix: 400 people over stairs give 4.0 m total width.
Description
Not yet checkable: occupancy is not stored as a typed value in the model.
Source
VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 7)
More rules for Fire protection directive 16-15 Escape and rescue routes
-
VKF-16-15-014
External stairs: definition and protected external walls
A stair system counts as an external stair if less than half of its plan area is enclosed by external building walls and half of the facade portion bordering the outside is permanently open, with evenly distributed openings that cannot be closed.
-
VKF-16-15-015
Horizontal escape routes: lead to the vertical route, subdivided above 50 m
Horizontal escape routes lead to a vertical escape route or to a safe place outside. If they are longer than 50 m, fire separations divide them so that escape routes of similar length result.
-
VKF-16-15-016
Access balconies: open, made of RF1, leading to the vertical escape route
Access balconies lead to vertical escape routes and consist of RF1 materials; linear load-bearing members may be combustible. They are permanently open to the outside for at least half, with evenly distributed openings that cannot be closed.