Rule Fire protection directive 16-15 Escape and rescue routes
External stairs: definition and protected external walls
VKF-16-15-014
pragmaticBIM.ch/vkf-16-15-014
A stair system counts as an external stair if less than half of its plan area is enclosed by external building walls and half of the facade portion bordering the outside is permanently open, with evenly distributed openings that cannot be closed.
Description
External stairs are placed so that a fire in or on the building does not endanger users. The adjoining external walls have fire resistance EI 30 (glazing and doors E 30) or consist of RF1 materials. From 1.2 m distance to the facade the requirements may be reduced appropriately. Not yet checkable: openness of the stair system and distance to the facade are not recorded in the model.
Source
VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 7)
More rules for Fire protection directive 16-15 Escape and rescue routes
-
VKF-16-15-015
Horizontal escape routes: lead to the vertical route, subdivided above 50 m
Horizontal escape routes lead to a vertical escape route or to a safe place outside. If they are longer than 50 m, fire separations divide them so that escape routes of similar length result.
-
VKF-16-15-016
Access balconies: open, made of RF1, leading to the vertical escape route
Access balconies lead to vertical escape routes and consist of RF1 materials; linear load-bearing members may be combustible. They are permanently open to the outside for at least half, with evenly distributed openings that cannot be closed.
-
VKF-16-15-017
Doors on rescue routes openable from outside, automatic doors suitable
Doors on rescue routes must be openable from outside by the emergency services. Automatic sliding and revolving doors are allowed on escape routes if they ensure escape at all times and are suitable for this use.