Rule Fire protection directive 16-15 Escape and rescue routes

External stairs: definition and protected external walls

VKF-16-15-014 pragmaticBIM.ch/vkf-16-15-014

A stair system counts as an external stair if less than half of its plan area is enclosed by external building walls and half of the facade portion bordering the outside is permanently open, with evenly distributed openings that cannot be closed.

Description

External stairs are placed so that a fire in or on the building does not endanger users. The adjoining external walls have fire resistance EI 30 (glazing and doors E 30) or consist of RF1 materials. From 1.2 m distance to the facade the requirements may be reduced appropriately. Not yet checkable: openness of the stair system and distance to the facade are not recorded in the model.

Source

VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 7)

More rules for Fire protection directive 16-15 Escape and rescue routes