Rule Fire protection directive 16-15 Escape and rescue routes
Room exits by occupancy
VKF-16-15-008
pragmaticBIM.ch/vkf-16-15-008
The number and width of a room's exits depend on its occupancy: up to 50 people one exit of 0.90 m; up to 100 people two of 0.90 m each; up to 200 people three of 0.90 m each or two of 0.90 m and 1.20 m; more than 200 people several of at least 1.20 m each.
Description
In office, commercial and industrial buildings 0.90 m exits are enough whatever the occupancy; that use exception is outside this check. The check reads PeakOccupancy (indoorenvironmentpeakoccupancy) and the OverallWidth of doors connecting the space.
Source
VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 7)
More rules for Fire protection directive 16-15 Escape and rescue routes
-
VKF-16-15-009
Doors on escape routes open in the escape direction
Doors on escape routes open in the escape direction and can be opened quickly in that direction at any time without a key or tool. For rooms for at most 20 people the swing direction is free; the check applies only when a connected space has PeakOccupancy above 20 or no occupancy is set.
-
VKF-16-15-010
Keep escape routes clear at all times and use them only for circulation
Escape and rescue routes may serve as ordinary circulation routes but must stay clear and safely usable at all times. Outside the use unit they must not serve any other purpose, for example as storage or waiting areas.
-
VKF-16-15-011
Vertical escape routes lead independently to the outside and are not offset
Vertical escape routes (e.g. stair systems) lead to a safe place outside. Where there are several, they lead there independently of each other.