Rule Fire protection directive 16-15 Escape and rescue routes

Room exits by occupancy

VKF-16-15-008 pragmaticBIM.ch/vkf-16-15-008

The number and width of a room's exits depend on its occupancy: up to 50 people one exit of 0.90 m; up to 100 people two of 0.90 m each; up to 200 people three of 0.90 m each or two of 0.90 m and 1.20 m; more than 200 people several of at least 1.20 m each.

Description

In office, commercial and industrial buildings 0.90 m exits are enough whatever the occupancy; that use exception is outside this check. The check reads PeakOccupancy (indoorenvironmentpeakoccupancy) and the OverallWidth of doors connecting the space.

Source

VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 7)