Rule Fire protection directive 16-15 Escape and rescue routes
Vertical escape routes lead independently to the outside and are not offset
VKF-16-15-011
pragmaticBIM.ch/vkf-16-15-011
Vertical escape routes (e.g. stair systems) lead to a safe place outside. Where there are several, they lead there independently of each other.
Description
Stairs and landings are built to be safely walkable, and a vertical escape route must not be offset from storey to storey. As guidance, the appendix gives a clear headroom of at least 2.1 m and intermediate landings at changes of direction, after at most 20 steps and at least at every storey. Not yet checkable: independence of routes, offsets and step geometry are not consistently represented in the model.
Source
VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 5)
More rules for Fire protection directive 16-15 Escape and rescue routes
-
VKF-16-15-012
Escape route within the use unit at most 35 m
Within a use unit the escape route may measure at most 35 m. If the exits do not lead directly outside or into a vertical escape route within these 35 m, a horizontal escape route is needed in between (e.g. a corridor with fire resistance or an access balcony).
-
VKF-16-15-013
Exit width above 200 people: 0.6 m per 100 or per 60 people
With an occupancy above 200 people, the exits together must be at least 0.6 m wide per 100 people where the route leads outside at ground level, and at least 0.6 m per 60 people where it leads over stairs. Example from the appendix: 400 people over stairs give 4.0 m total width.
-
VKF-16-15-014
External stairs: definition and protected external walls
A stair system counts as an external stair if less than half of its plan area is enclosed by external building walls and half of the facade portion bordering the outside is permanently open, with evenly distributed openings that cannot be closed.