Rule Fire protection directive 16-15 Escape and rescue routes
Doors on escape routes open in the escape direction
VKF-16-15-009
pragmaticBIM.ch/vkf-16-15-009
Doors on escape routes open in the escape direction and can be opened quickly in that direction at any time without a key or tool. For rooms for at most 20 people the swing direction is free; the check applies only when a connected space has PeakOccupancy above 20 or no occupancy is set.
Description
Gates and revolving doors need a normally swinging door next to them; that is outside this check. The check reads opensinescapedirection on doors on the escape route.
Source
VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 8)
More rules for Fire protection directive 16-15 Escape and rescue routes
-
VKF-16-15-010
Keep escape routes clear at all times and use them only for circulation
Escape and rescue routes may serve as ordinary circulation routes but must stay clear and safely usable at all times. Outside the use unit they must not serve any other purpose, for example as storage or waiting areas.
-
VKF-16-15-011
Vertical escape routes lead independently to the outside and are not offset
Vertical escape routes (e.g. stair systems) lead to a safe place outside. Where there are several, they lead there independently of each other.
-
VKF-16-15-012
Escape route within the use unit at most 35 m
Within a use unit the escape route may measure at most 35 m. If the exits do not lead directly outside or into a vertical escape route within these 35 m, a horizontal escape route is needed in between (e.g. a corridor with fire resistance or an access balcony).