Rule Fire protection directive 16-15 Escape and rescue routes
Keep escape routes clear at all times and use them only for circulation
VKF-16-15-010
pragmaticBIM.ch/vkf-16-15-010
Escape and rescue routes may serve as ordinary circulation routes but must stay clear and safely usable at all times. Outside the use unit they must not serve any other purpose, for example as storage or waiting areas.
Description
Not yet checkable: furniture and stored goods in an escape route are not clearly assigned to a use in the model.
Source
VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 5)
More rules for Fire protection directive 16-15 Escape and rescue routes
-
VKF-16-15-011
Vertical escape routes lead independently to the outside and are not offset
Vertical escape routes (e.g. stair systems) lead to a safe place outside. Where there are several, they lead there independently of each other.
-
VKF-16-15-012
Escape route within the use unit at most 35 m
Within a use unit the escape route may measure at most 35 m. If the exits do not lead directly outside or into a vertical escape route within these 35 m, a horizontal escape route is needed in between (e.g. a corridor with fire resistance or an access balcony).
-
VKF-16-15-013
Exit width above 200 people: 0.6 m per 100 or per 60 people
With an occupancy above 200 people, the exits together must be at least 0.6 m wide per 100 people where the route leads outside at ground level, and at least 0.6 m per 60 people where it leads over stairs. Example from the appendix: 400 people over stairs give 4.0 m total width.