Rule Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
Pipes through compartment components: recognized firestop system
VKF-15-15-012
pragmaticBIM.ch/vkf-15-15-012
Where pipes pass through components that form fire compartments, a VKF-recognized firestop system is used, e.g. a fire collar.
Description
Exceptions apply among others to pipes made of RF1 materials, to pipes entering, leaving or running inside fire-resistant installation shafts, to single pipes up to 50 mm outer diameter, in low and medium-height buildings to single pipes up to 120 mm where smoke causes no increased risk to people, to cavity-free filled sanitary pre-wall systems, and between rooms protected by an extinguishing system. Not yet checkable: pipe diameter and material are mostly not defined in the model.
Source
VKF-Brandschutzrichtlinie 15-15 Brandschutzabstände, Tragwerke, Brandabschnitte (2015) (p. 9)
More rules for Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
-
VKF-15-15-013
Combustible pipe insulation interrupted at the penetration
Combustible thermal insulation on services is interrupted with RF1 material where the service passes through a wall or floor that forms a fire compartment. For tested and recognized components the VKF recognition applies.
-
VKF-15-15-014
Installation shafts over several storeys: compartment-forming, at least EI 30
Building-services lines running over several storeys are in principle routed in installation shafts that themselves form fire compartments. The shaft enclosure matches the fire resistance of the use-related compartmentation, but at least EI 30.
-
VKF-15-15-015
Inspection openings of installation shafts: EI 30 closure
Inspection openings in installation shafts are closed with fire-rated closures EI 30. In low and medium-height buildings RF1 inspection covers are sufficient where the shaft is subdivided or filled storey by storey.