Rule Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments

Pipes through compartment components: recognized firestop system

VKF-15-15-012 pragmaticBIM.ch/vkf-15-15-012

Where pipes pass through components that form fire compartments, a VKF-recognized firestop system is used, e.g. a fire collar.

Description

Exceptions apply among others to pipes made of RF1 materials, to pipes entering, leaving or running inside fire-resistant installation shafts, to single pipes up to 50 mm outer diameter, in low and medium-height buildings to single pipes up to 120 mm where smoke causes no increased risk to people, to cavity-free filled sanitary pre-wall systems, and between rooms protected by an extinguishing system. Not yet checkable: pipe diameter and material are mostly not defined in the model.

Source

VKF-Brandschutzrichtlinie 15-15 Brandschutzabstände, Tragwerke, Brandabschnitte (2015) (p. 9)