Element

Pipe (schematic)

MEP-SCH-PIPE pragmaticBIM.ch/mep-sch-pipe

Reserves main pipework routes in the initial phase and reduces later clashes.

Pipe (schematic) (MEP-SCH-PIPE)

Description

  • Simplified segment or volume for main routes (heating, cooling, water, wastewater, etc.).
  • Used for feasibility and clash checking, not for execution planning.

Modelling guidelines

  • Model as a volume or simplified segment; cross-section according to the sketch concept.
  • Set the medium in Reference (e.g. HZ, KZ, TW, AW, ENT).
  • Use only in preliminary design. From the construction project onward, the downpipe is a separate element with Reference FL.
  • Do not model fittings, control valves, or connection details.

IFC entity

IFC4
IfcPipeSegment
IFC4.3
IfcPipeSegment
IFC2x3
IfcFlowSegment
Applicability rule
(entity_ifc4=IfcPipeSegment AND (Reference=HZ OR Reference=VL-H OR Reference=RL-H OR Reference=KZ OR Reference=VL-K OR Reference=RL-K OR Reference=TW OR Reference=FW OR Reference=AW OR Reference=WW OR Reference=ENT)) OR (entity_ifc2x3=IfcFlowSegment AND (Reference=HZ OR Reference=VL-H OR Reference=RL-H OR Reference=KZ OR Reference=VL-K OR Reference=RL-K OR Reference=TW OR Reference=FW OR Reference=AW OR Reference=WW OR Reference=ENT))

Attributes

Reference Pset_PipeSegmentTypeCommon

Medium of the schematic pipe.

Allowed values

  • HZ - heating
  • VL-H - heating flow (supply)
  • RL-H - heating return
  • KZ - cooling
  • VL-K - cooling flow (supply)
  • RL-K - cooling return
  • TW - drinking water
  • FW - fresh water
  • AW - wastewater (sanitary)
  • WW - wastewater (alternate code)
  • ENT - drainage (building)
+1 more
Status Pset_PipeSegmentTypeCommon

Component status for coordinating work in existing buildings.

Allowed values

  • NEW - new build
  • EXISTING - existing
  • DEMOLISH - demolition
  • TEMPORARY - temporary
ElementStatus ePset_ElementStatus

Component status for coordinating work in existing buildings.

Allowed values

  • NEW - new build
  • EXISTING - existing
  • DEMOLISH - demolition
  • TEMPORARY - temporary

Note

  • IFC2x3 substitute for Status.
FundingApplication ePset_Cost

Number of the funding application, so quantities and costs can be filtered by application. Separate several numbers with commas, e.g. 2024-0142, 2024-0188. Leave empty when the component belongs to no application.

GrossCrossSectionArea Qto_PipeSegmentBaseQuantities · m²

Cross-sectional area of the modelled schematic pipe.

Related elements