Rule Fire protection directive 14-15 Use of building materials
Interior fit-out: thin coatings and linear substructures where RF1/RF2 is required
VKF-14-15-014
pragmaticBIM.ch/vkf-14-15-014
Where RF1 is required for interior walls, floors and ceilings, combustible coatings such as paint, wallpaper or veneer up to 1.5 mm thick are allowed on the room side. Where RF1 or RF2 is required, linear substructures such as battens may be RF3, provided the visible side has a closed layer of the required group.
Description
Not yet checkable: the model does not carry the reaction-to-fire group (RF1 - RF4, cr) of materials.
Source
VKF-Brandschutzrichtlinie 14-15 Verwendung von Baustoffen (2015) (p. 9)
More rules for Fire protection directive 14-15 Use of building materials
-
VKF-14-15-001
High-rise buildings: external wall and cladding system made of RF1 materials
The external wall and the external wall cladding system of high-rise buildings are made of RF1 materials. Exceptions are plastic anchors, point back-anchorages of insulation and components of negligible area such as joints or seals.
-
VKF-14-15-002
High-rise buildings: external wall with combustible layers encapsulated on all sides K 60
Where a high-rise external wall consists of single layers containing combustible materials, it counts as RF1 as a whole if it is encapsulated on all sides with K 60 - RF1. The gaps are filled without voids with RF1 materials.
-
VKF-14-15-015
Evacuation rooms, airlocks and anterooms: assignment to escape routes
For materials, evacuation rooms count as vertical escape routes, except patient rooms and horizontal escape routes in accommodation. Airlocks count as vertical escape routes, anterooms as horizontal ones.