Rule Fire protection directive 14-15 Use of building materials
Escape routes: combustible area share at most 10 %
VKF-14-15-012
pragmaticBIM.ch/vkf-14-15-012
In escape routes, the area share of combustible materials such as luminous panels, pin boards, linings or balustrade infills is at most 10 % of the stairwell floor area per storey or of the floor area of the horizontal escape route. Partial areas are at most 2 m² and keep at least 2 m distance from each other.
Description
Doors, windows, handrails and individual linear load-bearing timber components are not counted. Not yet checkable: the model does not carry the reaction-to-fire group (RF1 - RF4, cr) of materials.
Source
VKF-Brandschutzrichtlinie 14-15 Verwendung von Baustoffen (2015) (p. 10)
More rules for Fire protection directive 14-15 Use of building materials
-
VKF-14-15-013
Other interior rooms: minimum reaction-to-fire requirements
In interior rooms outside escape routes, RF3 materials generally suffice in low and medium-height buildings. Exceptions: in accommodation and rooms with large occupancy, stretched ceilings are RF1 with a structural concept and RF2 with an extinguishing-system concept.
-
VKF-14-15-014
Interior fit-out: thin coatings and linear substructures where RF1/RF2 is required
Where RF1 is required for interior walls, floors and ceilings, combustible coatings such as paint, wallpaper or veneer up to 1.5 mm thick are allowed on the room side. Where RF1 or RF2 is required, linear substructures such as battens may be RF3, provided the visible side has a closed layer of the required group.
-
VKF-14-15-015
Evacuation rooms, airlocks and anterooms: assignment to escape routes
For materials, evacuation rooms count as vertical escape routes, except patient rooms and horizontal escape routes in accommodation. Airlocks count as vertical escape routes, anterooms as horizontal ones.