Rule Fire protection directive 26-15 Hazardous substances
Containers and small tanks: requirement for room or cabinet by stored quantity (25 l to over 2,000 l) and flash point
VKF-26-15-014
pragmaticBIM.ch/vkf-26-15-014
For combustible liquids with a flash point up to 60 °C, per compartment: up to 25 l a room of any construction; 26 - 100 l an RF1 cabinet with collecting tray and marking; 101 - 450 l a room EI 30 with low fire risk; 451 - 2,000 l a room EI 60 without additional fire loads; above 2,000 l a room EI 90 without...
Description
For combustible liquids with a flash point up to 60 °C, per compartment: up to 25 l a room of any construction; 26 - 100 l an RF1 cabinet with collecting tray and marking; 101 - 450 l a room EI 30 with low fire risk; 451 - 2,000 l a room EI 60 without additional fire loads; above 2,000 l a room EI 90 without additional fire loads. For a flash point above 60 °C: up to 25 l any; 26 - 450 l an RF1 cabinet with collecting tray and marking; 451 - 2,000 l a room EI 30 with low fire risk; above 2,000 l a room EI 60 without additional fire loads. A cabinet to SN EN 14470-1 with matching fire resistance can replace a room. Not yet checkable: the model does not show flash point, stored volume, container type and fire resistance of the storage room.
Source
VKF-Brandschutzrichtlinie 26-15 Gefährliche Stoffe (2015) (p. 10)
More rules for Fire protection directive 26-15 Hazardous substances
-
VKF-26-15-015
Medium-sized tanks: up to 10,000 l flash point ≤ 60 °C in a room EI 90, up to 250,000 l above that in a room EI 60
In a room EI 90 without additional fire loads, at most 10,000 l of combustible liquids with a flash point up to 60 °C may be stored; special protective measures are needed (e.g. mechanical ventilation, extinguishing system, gas detection).
-
VKF-26-15-016
Ventilation for highly flammable liquids: natural openings 20 cm² per m², artificial 3 to 5 air changes, 10 during handling
Storage rooms count as sufficiently naturally ventilated when above ground with at least two opposite non-closable openings to the outside, one of them at most 0.1 m above the floor, each at least 20 cm² per m² of floor area.
-
VKF-26-15-017
Oxidising substances: from 100 kg own fire compartment EI 60, outdoors 5 m distance or screen wall EI 60
Oxidisers may be stored with other hazardous substances in the same compartment up to 100 kg in total, if 2.5 m distance to combustible materials is kept or partition walls EI 30 of RF1 are installed.