Containers and small tanks: requirement for room or cabinet by stored quantity (25 l to over 2,000 l) and flash point

VKF-26-15-014 pragmaticBIM.ch/vkf-26-15-014

For combustible liquids with a flash point up to 60 °C, per compartment: up to 25 l a room of any construction; 26 - 100 l an RF1 cabinet with collecting tray and marking; 101 - 450 l a room EI 30 with low fire risk; 451 - 2,000 l a room EI 60 without additional fire loads; above 2,000 l a room EI 90 without...

Description

For combustible liquids with a flash point up to 60 °C, per compartment: up to 25 l a room of any construction; 26 - 100 l an RF1 cabinet with collecting tray and marking; 101 - 450 l a room EI 30 with low fire risk; 451 - 2,000 l a room EI 60 without additional fire loads; above 2,000 l a room EI 90 without additional fire loads. For a flash point above 60 °C: up to 25 l any; 26 - 450 l an RF1 cabinet with collecting tray and marking; 451 - 2,000 l a room EI 30 with low fire risk; above 2,000 l a room EI 60 without additional fire loads. A cabinet to SN EN 14470-1 with matching fire resistance can replace a room. Not yet checkable: the model does not show flash point, stored volume, container type and fire resistance of the storage room.

Source

VKF-Brandschutzrichtlinie 26-15 Gefährliche Stoffe (2015) (p. 10)