Rule Fire protection directive 26-15 Hazardous substances

Medium-sized tanks: up to 10,000 l flash point ≤ 60 °C in a room EI 90, up to 250,000 l above that in a room EI 60

VKF-26-15-015 pragmaticBIM.ch/vkf-26-15-015

In a room EI 90 without additional fire loads, at most 10,000 l of combustible liquids with a flash point up to 60 °C may be stored; special protective measures are needed (e.g. mechanical ventilation, extinguishing system, gas detection).

Description

In a room EI 60 without additional fire loads, at most 250,000 l of combustible liquids with a flash point above 60 °C may be stored. Not yet checkable: the model does not show flash point, stored volume, container type and fire resistance of the storage room.

Source

VKF-Brandschutzrichtlinie 26-15 Gefährliche Stoffe (2015) (p. 11)

More rules for Fire protection directive 26-15 Hazardous substances

Contact

abstract ag

Imprint · Picassoplatz 4, 4052 Basel