Rule Fire protection directive 26-15 Hazardous substances
Medium-sized tanks: up to 10,000 l flash point ≤ 60 °C in a room EI 90, up to 250,000 l above that in a room EI 60
VKF-26-15-015
pragmaticBIM.ch/vkf-26-15-015
In a room EI 90 without additional fire loads, at most 10,000 l of combustible liquids with a flash point up to 60 °C may be stored; special protective measures are needed (e.g. mechanical ventilation, extinguishing system, gas detection).
Description
In a room EI 60 without additional fire loads, at most 250,000 l of combustible liquids with a flash point above 60 °C may be stored. Not yet checkable: the model does not show flash point, stored volume, container type and fire resistance of the storage room.
Source
VKF-Brandschutzrichtlinie 26-15 Gefährliche Stoffe (2015) (p. 11)
More rules for Fire protection directive 26-15 Hazardous substances
-
VKF-26-15-016
Ventilation for highly flammable liquids: natural openings 20 cm² per m², artificial 3 to 5 air changes, 10 during handling
Storage rooms count as sufficiently naturally ventilated when above ground with at least two opposite non-closable openings to the outside, one of them at most 0.1 m above the floor, each at least 20 cm² per m² of floor area.
-
VKF-26-15-017
Oxidising substances: from 100 kg own fire compartment EI 60, outdoors 5 m distance or screen wall EI 60
Oxidisers may be stored with other hazardous substances in the same compartment up to 100 kg in total, if 2.5 m distance to combustible materials is kept or partition walls EI 30 of RF1 are installed.
-
VKF-26-15-018
Substances with special fire behaviour: closed RF1 containers, dry, stock above need in a separate marked room
Self-igniting substances are kept in closed RF1 containers excluding air, in an inert atmosphere or under regular temperature monitoring.