Rule Fire protection directive 26-15 Hazardous substances

Ventilation for highly flammable liquids: natural openings 20 cm² per m², artificial 3 to 5 air changes, 10 during handling

VKF-26-15-016 pragmaticBIM.ch/vkf-26-15-016

Storage rooms count as sufficiently naturally ventilated when above ground with at least two opposite non-closable openings to the outside, one of them at most 0.1 m above the floor, each at least 20 cm² per m² of floor area.

Description

Other rooms (e.g. below-ground rooms) are ventilated artificially: 3 to 5 air changes per hour with extraction points at most 0.1 m above the floor. Intermittent operation by timer must switch on automatically when the room is entered and when equipment runs; if a gas warning system controls it, continuous or intermittent ventilation can be omitted. For handling without a closed system or extraction, 10 air changes per hour apply, with extraction also at most 0.1 m above the floor. Not yet checkable: the model does not show flash point, stored volume, container type and fire resistance of the storage room.

Source

VKF-Brandschutzrichtlinie 26-15 Gefährliche Stoffe (2015) (p. 11)