Storage rooms for combustible liquids: EI 30 doors, access opening at least 0.7 × 1 m with an EI 30 cover

VKF-26-15-013 pragmaticBIM.ch/vkf-26-15-013

Storage rooms for combustible liquids are closed off from other rooms with EI 30 doors. Access to tank rooms is by openings of at least 0.7 × 1 m, closed with EI 30 covers.

Description

Heating oil up to 4,000 l in small tanks or 8,000 l in steel tanks may be stored in separate boiler rooms EI 60. Not yet checkable: the model does not show flash point, stored volume, container type and fire resistance of the storage room.

Source

VKF-Brandschutzrichtlinie 26-15 Gefährliche Stoffe (2015) (p. 10)