Rule Fire protection directive 26-15 Hazardous substances

Combustible liquids: prevent spreading, vapours not into lower rooms, flash point ≤ 23 °C only in permitted containers

VKF-26-15-012 pragmaticBIM.ch/vkf-26-15-012

Leaking combustible liquids must not spread (e.g. raised door thresholds, drainage channels, separators, drip trays), and their vapours must not reach lower rooms, sewers, shafts or pits. Heating devices are thermally secured; no heating with open flames or unprotected heat sources.

Description

Liquids with a flash point up to 23 °C are stored in containers or small tanks, in pressure-shock-resistant metal tanks with domed ends (tested at 4 bar) or in vertical cylindrical steel tanks with flat bottoms. Not yet checkable: the model does not show flash point, stored volume, container type and fire resistance of the storage room.

Source

VKF-Brandschutzrichtlinie 26-15 Gefährliche Stoffe (2015) (p. 9)