Rule Fire protection directive 26-15 Hazardous substances
Rooms at fire or explosion risk: zones, pressure relief and fire compartment; storage rooms as fire compartments
VKF-26-15-004
pragmaticBIM.ch/vkf-26-15-004
Rooms are classified by fire and explosion hazard and divided into zones; type, quantity, frequency and duration of combustible gases, dusts or vapours decide.
Description
Rooms with fire or explosion hazard have pressure relief (e.g. a light exterior wall) or equivalent measures and are built as fire compartments; relief areas must not endanger the surroundings disproportionately. Storage rooms for hazardous substances are fire compartments and, where needed, protected or monitored. Not yet checkable: the model does not show substance classification, stored quantity, type and location of hazardous substances.
Source
VKF-Brandschutzrichtlinie 26-15 Gefährliche Stoffe (2015) (p. 7)
More rules for Fire protection directive 26-15 Hazardous substances
-
VKF-26-15-005
Ventilation of hazardous concentrations; fans and ignition sources in hazard zones
Rooms or zones where combustible gases, vapours, mists or dusts can accumulate dangerously are ventilated naturally or artificially to a sufficient extent. Fans and their drives in explosion-hazard zones or in exhaust ducts must not become effective ignition sources.
-
VKF-26-15-006
Lightning protection: gases above 1,000 kg, combustible liquids above 2,000 l, tyre stores, large pyrotechnic stores
Buildings and plant holding hazardous substances are protected against ignition by lightning. Combustible gases: up to 450 kg net no measures, up to 1,000 kg earthing or equipotential bonding of conductive parts, above that a lightning protection system.
-
VKF-26-15-007
Extinguishing equipment in hazard buildings; fire alarm, gas warning or extinguishing systems as needed
In buildings and plant with rooms or zones at fire or explosion risk, suitable extinguishing equipment is installed at suitable places and in sufficient number. Where conditions require it, fire alarm systems, gas warning systems or extinguishing systems are added.