Rule Fire protection directive 26-15 Hazardous substances
Lightning protection: gases above 1,000 kg, combustible liquids above 2,000 l, tyre stores, large pyrotechnic stores
VKF-26-15-006
pragmaticBIM.ch/vkf-26-15-006
Buildings and plant holding hazardous substances are protected against ignition by lightning. Combustible gases: up to 450 kg net no measures, up to 1,000 kg earthing or equipotential bonding of conductive parts, above that a lightning protection system.
Description
Combustible liquids with a flash point up to 60 °C: up to 450 l nothing, up to 2,000 l earthing or equipotential bonding, above that a lightning protection system. Buildings with a tyre store above 60 t or 600 m² and large stores of pyrotechnic articles above 300 kg are protected against lightning. Not yet checkable: the model does not show substance classification, stored quantity, type and location of hazardous substances.
Source
VKF-Brandschutzrichtlinie 26-15 Gefährliche Stoffe (2015) (p. 7)
More rules for Fire protection directive 26-15 Hazardous substances
-
VKF-26-15-007
Extinguishing equipment in hazard buildings; fire alarm, gas warning or extinguishing systems as needed
In buildings and plant with rooms or zones at fire or explosion risk, suitable extinguishing equipment is installed at suitable places and in sufficient number. Where conditions require it, fire alarm systems, gas warning systems or extinguishing systems are added.
-
VKF-26-15-008
Storage concept, substance segregation in separate fire compartments and hazard signs
A storage concept is drawn up for stores with hazardous substances (inventory, location, type and container, structural, technical and organisational measures).
-
VKF-26-15-009
Gas cylinders: not in escape routes, ventilated, from 200 l cylinder volume outdoors or in a separate fire compartment
Gas cylinders are protected against excessive heating, mechanical damage and falling over and are not stored together with highly flammable or self-igniting substances. In escape routes they are neither connected nor stored; rooms with connected or stored cylinders are sufficiently ventilated.