Rule Fire protection directive 25-15 Ventilation systems

Air-handling units serving several ventilation sections: separate room with EI 30 and EI 30 doors

VKF-25-15-001 pragmaticBIM.ch/vkf-25-15-001

Units that serve several ventilation sections are installed in a separate room. Its enclosure matches the fire resistance of the use-related compartmentation, but at least EI 30; the doors are also EI 30.

Description

Units serving only one ventilation section may be placed freely, and air-treatment units for single-room ventilation may stand in the room they ventilate. Not yet checkable: the model does not show ventilation sections or which fire compartments a unit supplies.

Source

VKF-Brandschutzrichtlinie 25-15 Lufttechnische Anlagen (2015) (p. 4)