Rule Fire protection directive 25-15 Ventilation systems
Air-handling units serving several ventilation sections: separate room with EI 30 and EI 30 doors
VKF-25-15-001
pragmaticBIM.ch/vkf-25-15-001
Units that serve several ventilation sections are installed in a separate room. Its enclosure matches the fire resistance of the use-related compartmentation, but at least EI 30; the doors are also EI 30.
Description
Units serving only one ventilation section may be placed freely, and air-treatment units for single-room ventilation may stand in the room they ventilate. Not yet checkable: the model does not show ventilation sections or which fire compartments a unit supplies.
Source
VKF-Brandschutzrichtlinie 25-15 Lufttechnische Anlagen (2015) (p. 4)
More rules for Fire protection directive 25-15 Ventilation systems
-
VKF-25-15-002
Outdoor air and exhaust air: safe intake and discharge
Outdoor air is taken directly from the open so that no combustible gases or vapours are drawn in. Exhaust-air ducts discharge to the open so that escaping fire gases and flames do not endanger the surroundings and cannot reach the outdoor-air intake.
-
VKF-25-15-003
Filters and silencers at least RF3, filter liquid with flash point above 160 °C
Filters and silencers are made of at least RF3 materials. Filter liquids have a flash point above 160 °C.
-
VKF-25-15-004
Fans and air-treatment units of RF1, safety devices on air heaters
Fans (except parts of no fire-safety significance) and air-treatment units with their built-in parts (air heaters, coolers, heat recovery, humidifiers) are made of RF1 materials.