Rule Fire protection directive 25-15 Ventilation systems
Cleaning, inspection and maintenance of ventilation systems and fire dampers
VKF-25-15-020
pragmaticBIM.ch/vkf-25-15-020
Ventilation systems are cleaned and maintained so that they are always ready for operation and no fire hazard arises. Fire dampers and fire-case controls are inspected periodically.
Description
Owners or operators are responsible for maintenance and operational readiness. This is an operating process; the model keeps no inspection or maintenance status.
Source
VKF-Brandschutzrichtlinie 25-15 Lufttechnische Anlagen (2015) (p. 11)
More rules for Fire protection directive 25-15 Ventilation systems
-
VKF-25-15-001
Air-handling units serving several ventilation sections: separate room with EI 30 and EI 30 doors
Units that serve several ventilation sections are installed in a separate room. Its enclosure matches the fire resistance of the use-related compartmentation, but at least EI 30; the doors are also EI 30.
-
VKF-25-15-002
Outdoor air and exhaust air: safe intake and discharge
Outdoor air is taken directly from the open so that no combustible gases or vapours are drawn in. Exhaust-air ducts discharge to the open so that escaping fire gases and flames do not endanger the surroundings and cannot reach the outdoor-air intake.
-
VKF-25-15-003
Filters and silencers at least RF3, filter liquid with flash point above 160 °C
Filters and silencers are made of at least RF3 materials. Filter liquids have a flash point above 160 °C.