Rule Fire protection directive 25-15 Ventilation systems
Ducts without openings through other sections: EI 30 or fire dampers
VKF-25-15-008
pragmaticBIM.ch/vkf-25-15-008
Ventilation ducts that run without openings through other fire or ventilation sections, or whose outlets are on the storey above or below, are built or clad with EI 30. In airlocks and vertical escape routes the fire resistance of the use-related compartmentation applies, at least EI 30.
Description
For ventilation sections, fire dampers may be installed instead. Installation shafts must not serve as ventilation ducts. Not yet checkable: the model shows neither which sections a duct passes through nor its fire resistance or cladding.
Source
VKF-Brandschutzrichtlinie 25-15 Lufttechnische Anlagen (2015) (p. 7)
More rules for Fire protection directive 25-15 Ventilation systems
-
VKF-25-15-009
Inspection and cleaning openings; no foreign installations in ventilation ducts
Ventilation ducts are arranged and fitted with openings so that they can be inspected and cleaned. Only parts that serve the system may be installed in ventilation ducts and air-carrying shafts (except ventilation ceilings and floors).
-
VKF-25-15-010
Duct penetration through compartment-forming components: firestop EI 30 or RF1 filling
The recess between the ventilation duct and the compartment-forming component is, allowing for thermal expansion, either filled tightly with RF1 materials (e.g. mortar, plaster) or closed with a firestop system that reaches EI 30 in compartment-forming walls and floors.
-
VKF-25-15-011
Fire dampers: at least EI 30-S, actuator, thermal release, self-closing
Fire dampers prevent fire and smoke from spreading through ventilation systems and are rated at least EI 30-S. They are fixed according to the declaration of performance or VKF technical information and the manufacturer's instructions, and are accessible and inspectable from outside.