Rule Fire protection directive 25-15 Ventilation systems
Inspection and cleaning openings; no foreign installations in ventilation ducts
VKF-25-15-009
pragmaticBIM.ch/vkf-25-15-009
Ventilation ducts are arranged and fitted with openings so that they can be inspected and cleaned. Only parts that serve the system may be installed in ventilation ducts and air-carrying shafts (except ventilation ceilings and floors).
Description
Ventilation systems, other than those with raised air temperature, need no safety distance to combustible material. Not yet checkable: inspection openings and foreign installations inside ducts are not held in the model.
Source
VKF-Brandschutzrichtlinie 25-15 Lufttechnische Anlagen (2015) (p. 7)
More rules for Fire protection directive 25-15 Ventilation systems
-
VKF-25-15-010
Duct penetration through compartment-forming components: firestop EI 30 or RF1 filling
The recess between the ventilation duct and the compartment-forming component is, allowing for thermal expansion, either filled tightly with RF1 materials (e.g. mortar, plaster) or closed with a firestop system that reaches EI 30 in compartment-forming walls and floors.
-
VKF-25-15-011
Fire dampers: at least EI 30-S, actuator, thermal release, self-closing
Fire dampers prevent fire and smoke from spreading through ventilation systems and are rated at least EI 30-S. They are fixed according to the declaration of performance or VKF technical information and the manufacturer's instructions, and are accessible and inspectable from outside.
-
VKF-25-15-012
Fire dampers where ducts cross fire compartments and ventilation sections
Fire dampers are placed where ventilation ducts pass through fire walls and compartment-forming walls and floors, and where ducts without openings run through other ventilation sections without having the required fire resistance themselves.