Rule Fire protection directive 25-15 Ventilation systems
Fans and air-treatment units of RF1, safety devices on air heaters
VKF-25-15-004
pragmaticBIM.ch/vkf-25-15-004
Fans (except parts of no fire-safety significance) and air-treatment units with their built-in parts (air heaters, coolers, heat recovery, humidifiers) are made of RF1 materials.
Description
Small fans, small built-in parts and heat recovery serving only one compartment or ventilation section may be at least RF3; insulation at least RF3 (cr), covered on all sides with at least 0.5 mm of RF1. Downstream of air heaters with heating surfaces above 150 °C, a safety temperature limiter within at most 1 m switches off at an air temperature of 85 °C; directly fired and electric air heaters have two independent safety devices and, above 3 kW, a fan overrun of at least 60 seconds. Not yet checkable: the material class of units and the safety devices (limiters, monitors) are not held in the model.
Source
VKF-Brandschutzrichtlinie 25-15 Lufttechnische Anlagen (2015) (p. 5)
More rules for Fire protection directive 25-15 Ventilation systems
-
VKF-25-15-005
Smoke trigger device at the extract connection of systems serving several ventilation sections
Systems that serve several ventilation sections (fire compartments combined for ventilation purposes) have a smoke trigger device at the extract connection. When it responds, it switches the system off and closes the fire dampers.
-
VKF-25-15-006
Ventilation ducts of RF1, exceptions at least RF3
Ventilation ducts, ventilation ceilings and floors are made of RF1 materials. At least RF3 is enough within the fire compartment of ventilation sections in office, school and dwelling units, for ventilation ceilings and floors within one compartment, for ducts cast in concrete and for earth registers.
-
VKF-25-15-007
Hangers and thermal insulation of ventilation ducts
Hangers and fixings of RF1 ducts are also RF1 (except vibration dampers and the like) and hold the duct securely for the required fire resistance duration. Thermal insulation of RF1 ducts is RF1; outdoor-air ducts may use at least RF3 (cr) if covered on all sides with at least 0.5 mm of RF1.