Rule Fire protection directive 25-15 Ventilation systems

Outdoor air and exhaust air: safe intake and discharge

VKF-25-15-002 pragmaticBIM.ch/vkf-25-15-002

Outdoor air is taken directly from the open so that no combustible gases or vapours are drawn in. Exhaust-air ducts discharge to the open so that escaping fire gases and flames do not endanger the surroundings and cannot reach the outdoor-air intake.

Description

Instead of going directly outside, air may also pass through rooms with permanently open openings to the outside, provided a fire damper with a duct smoke detector is installed there. Not yet checkable: the model does not hold the position of outdoor-air and exhaust-air openings or their distance to each other.

Source

VKF-Brandschutzrichtlinie 25-15 Lufttechnische Anlagen (2015) (p. 5)

More rules for Fire protection directive 25-15 Ventilation systems