Rule Fire protection directive 25-15 Ventilation systems
Outdoor air and exhaust air: safe intake and discharge
VKF-25-15-002
pragmaticBIM.ch/vkf-25-15-002
Outdoor air is taken directly from the open so that no combustible gases or vapours are drawn in. Exhaust-air ducts discharge to the open so that escaping fire gases and flames do not endanger the surroundings and cannot reach the outdoor-air intake.
Description
Instead of going directly outside, air may also pass through rooms with permanently open openings to the outside, provided a fire damper with a duct smoke detector is installed there. Not yet checkable: the model does not hold the position of outdoor-air and exhaust-air openings or their distance to each other.
Source
VKF-Brandschutzrichtlinie 25-15 Lufttechnische Anlagen (2015) (p. 5)
More rules for Fire protection directive 25-15 Ventilation systems
-
VKF-25-15-003
Filters and silencers at least RF3, filter liquid with flash point above 160 °C
Filters and silencers are made of at least RF3 materials. Filter liquids have a flash point above 160 °C.
-
VKF-25-15-004
Fans and air-treatment units of RF1, safety devices on air heaters
Fans (except parts of no fire-safety significance) and air-treatment units with their built-in parts (air heaters, coolers, heat recovery, humidifiers) are made of RF1 materials.
-
VKF-25-15-005
Smoke trigger device at the extract connection of systems serving several ventilation sections
Systems that serve several ventilation sections (fire compartments combined for ventilation purposes) have a smoke trigger device at the extract connection. When it responds, it switches the system off and closes the fire dampers.