Rule Fire protection directive 25-15 Ventilation systems
Filters and silencers at least RF3, filter liquid with flash point above 160 °C
VKF-25-15-003
pragmaticBIM.ch/vkf-25-15-003
Filters and silencers are made of at least RF3 materials. Filter liquids have a flash point above 160 °C.
Description
Not yet checkable: filters and silencers are not separate elements in the model and carry no reaction to fire.
Source
VKF-Brandschutzrichtlinie 25-15 Lufttechnische Anlagen (2015) (p. 5)
More rules for Fire protection directive 25-15 Ventilation systems
-
VKF-25-15-004
Fans and air-treatment units of RF1, safety devices on air heaters
Fans (except parts of no fire-safety significance) and air-treatment units with their built-in parts (air heaters, coolers, heat recovery, humidifiers) are made of RF1 materials.
-
VKF-25-15-005
Smoke trigger device at the extract connection of systems serving several ventilation sections
Systems that serve several ventilation sections (fire compartments combined for ventilation purposes) have a smoke trigger device at the extract connection. When it responds, it switches the system off and closes the fire dampers.
-
VKF-25-15-006
Ventilation ducts of RF1, exceptions at least RF3
Ventilation ducts, ventilation ceilings and floors are made of RF1 materials. At least RF3 is enough within the fire compartment of ventilation sections in office, school and dwelling units, for ventilation ceilings and floors within one compartment, for ducts cast in concrete and for earth registers.