Rule Fire protection directive 24-15 Heating plant
Ban on installing heat generators in escape routes, explosion-hazard rooms and rooms with high fire load
VKF-24-15-002
pragmaticBIM.ch/vkf-24-15-002
Heat generators must not be installed in escape routes, in rooms and zones with fire or explosion hazard, or in rooms with large and very large fire load. Not yet checkable: the model does not show nominal heat output, fuel, type of installation and fire resistance of the boiler room.
Source
VKF-Brandschutzrichtlinie 24-15 Wärmetechnische Anlagen (2015) (p. 5)
More rules for Fire protection directive 24-15 Heating plant
-
VKF-24-15-003
Single-family houses and flats: solid-fuel firing units in a room with EI 30
For liquid and gaseous fuels the construction and finish of the installation room are unrestricted.
-
VKF-24-15-004
Boiler room in buildings with several compartments: EI 30 up to 70 kW, EI 60 above, doors EI 30
Firing units stand in separate boiler rooms. Their fire resistance depends on the total nominal heat output: up to 70 kW the use-related compartment value, at least EI 30; above that at least EI 60.
-
VKF-24-15-005
Boiler room with direct access from outdoors: above 1,200 kW on ground floor or lower, above 600 kW from 2nd basement
Boiler rooms on the ground floor or lower for plants above 1,200 kW nominal heat output, and boiler rooms on the second basement or lower for plants above 600 kW, get direct access from outdoors.