Rule Fire protection directive 24-15 Heating plant

Fireplaces, tiled stoves, pellet firing units, commercial kitchens and cookers

VKF-24-15-011 pragmaticBIM.ch/vkf-24-15-011

For fireplaces the information of the declaration of performance or VKF technical information applies. Tiled and storage stoves keep 0.2 m at the sides, back and top and 0.5 m at the firing opening from combustibles and have cleaning openings.

Description

Commercial kitchens are separated from adjoining compartments with the compartmentation value, at least EI 30; with an open connection to the restaurant, ceiling skirts of RF1 or hoods with extinguishing equipment are needed. Walls behind gas cookers are EI 30 of RF1 and at least 60 mm thick. Not yet checkable: the model does not show surface temperature, combustibility of surroundings and clearances.

Source

VKF-Brandschutzrichtlinie 24-15 Wärmetechnische Anlagen (2015) (p. 8)