Rule Fire protection directive 24-15 Heating plant
Fireplaces, tiled stoves, pellet firing units, commercial kitchens and cookers
VKF-24-15-011
pragmaticBIM.ch/vkf-24-15-011
For fireplaces the information of the declaration of performance or VKF technical information applies. Tiled and storage stoves keep 0.2 m at the sides, back and top and 0.5 m at the firing opening from combustibles and have cleaning openings.
Description
Commercial kitchens are separated from adjoining compartments with the compartmentation value, at least EI 30; with an open connection to the restaurant, ceiling skirts of RF1 or hoods with extinguishing equipment are needed. Walls behind gas cookers are EI 30 of RF1 and at least 60 mm thick. Not yet checkable: the model does not show surface temperature, combustibility of surroundings and clearances.
Source
VKF-Brandschutzrichtlinie 24-15 Wärmetechnische Anlagen (2015) (p. 8)
More rules for Fire protection directive 24-15 Heating plant
-
VKF-24-15-012
Mobile firing units and small appliances: clearance, combustion air, no continuous heating without flue
Mobile firing units such as building dryers or air heaters keep as much distance from combustibles as comparable stationary units, need sufficient combustion air and, without direct flue routing, stand only in open halls, shells or well-ventilated rooms, not openly in rooms with large occupancy.
-
VKF-24-15-013
Flue systems: system flues, suitable materials, RF1 insulation, classification and marking
Flue systems and connecting pipes discharge the flue gases safely, can be cleaned and create no fire hazard. Only system flues made of heat-resistant construction products and suitable materials are used; thermal insulation is RF1.
-
VKF-24-15-014
Flue systems: connections, continuous routing and minimum height above roof
Only units that in normal operation do not produce flue gases hotter than the system allows are connected; connecting pipes enter in the same storey and fire compartment.