Rule Fire protection directive 24-15 Heating plant
Mobile firing units and small appliances: clearance, combustion air, no continuous heating without flue
VKF-24-15-012
pragmaticBIM.ch/vkf-24-15-012
Mobile firing units such as building dryers or air heaters keep as much distance from combustibles as comparable stationary units, need sufficient combustion air and, without direct flue routing, stand only in open halls, shells or well-ventilated rooms, not openly in rooms with large occupancy.
Description
Small appliances for cooking, decoration and lighting with liquid fuels keep sufficient distance from combustibles; from 0.3 l/h or 2 kW a flue system is needed, and without connection they must not heat rooms permanently. Not yet checkable: the model does not show surface temperature, combustibility of surroundings and clearances.
Source
VKF-Brandschutzrichtlinie 24-15 Wärmetechnische Anlagen (2015) (p. 9)
More rules for Fire protection directive 24-15 Heating plant
-
VKF-24-15-013
Flue systems: system flues, suitable materials, RF1 insulation, classification and marking
Flue systems and connecting pipes discharge the flue gases safely, can be cleaned and create no fire hazard. Only system flues made of heat-resistant construction products and suitable materials are used; thermal insulation is RF1.
-
VKF-24-15-014
Flue systems: connections, continuous routing and minimum height above roof
Only units that in normal operation do not produce flue gases hotter than the system allows are connected; connecting pipes enter in the same storey and fire compartment.
-
VKF-24-15-015
Flue systems through compartments: EI 60 vertically, compartment value horizontally, distance to combustibles, fill-in
Flue systems running vertically through several compartments have EI 60 of heat-resistant RF1 outside the installation room or sit in such a fire protection element, in single-family houses and flats EI 30; horizontally the fire resistance of the compartment applies.