Rule Fire protection directive 24-15 Heating plant
Flue systems: system flues, suitable materials, RF1 insulation, classification and marking
VKF-24-15-013
pragmaticBIM.ch/vkf-24-15-013
Flue systems and connecting pipes discharge the flue gases safely, can be cleaned and create no fire hazard. Only system flues made of heat-resistant construction products and suitable materials are used; thermal insulation is RF1.
Description
The systems are classified by temperature, pressure, condensate and corrosion resistance, soot-fire resistance, distance to combustibles, thermal resistance and fire resistance, and are clearly marked with these criteria, pressure class, cleaning method, manufacturer and installer. Not yet checkable: the model holds no flue system with classification, routing, minimum height above roof and clearance.
Source
VKF-Brandschutzrichtlinie 24-15 Wärmetechnische Anlagen (2015) (p. 10)
More rules for Fire protection directive 24-15 Heating plant
-
VKF-24-15-014
Flue systems: connections, continuous routing and minimum height above roof
Only units that in normal operation do not produce flue gases hotter than the system allows are connected; connecting pipes enter in the same storey and fire compartment.
-
VKF-24-15-015
Flue systems through compartments: EI 60 vertically, compartment value horizontally, distance to combustibles, fill-in
Flue systems running vertically through several compartments have EI 60 of heat-resistant RF1 outside the installation room or sit in such a fire protection element, in single-family houses and flats EI 30; horizontally the fire resistance of the compartment applies.
-
VKF-24-15-016
Explosion flaps, flue fans and cleaning openings
For fuels prone to deflagration, such as fine-grained coal or wood chips, explosion flaps belong in the flue system, in the boiler room close to the connecting pipe entry and at least the cross-section of the flue. Flue fans create positive pressure only if the system is approved for it.