Rule Fire protection directive 24-15 Heating plant
Flue systems: connections, continuous routing and minimum height above roof
VKF-24-15-014
pragmaticBIM.ch/vkf-24-15-014
Only units that in normal operation do not produce flue gases hotter than the system allows are connected; connecting pipes enter in the same storey and fire compartment.
Description
Common flues under negative pressure are allowed for up to four connections and 70 kW total output; units above 70 kW, open fireplaces and positive-pressure units need separate flues. Flues run continuously, if possible vertically, above the roof: 1 m for discharge in the roof surface, 0.5 m at the ridge or on non-accessible flat roofs, 2 m on accessible flat roofs; with less than 3 m distance to higher building parts, up above them. Not yet checkable: the model holds no flue system with classification, routing, minimum height above roof and clearance.
Source
VKF-Brandschutzrichtlinie 24-15 Wärmetechnische Anlagen (2015) (p. 11)
More rules for Fire protection directive 24-15 Heating plant
-
VKF-24-15-015
Flue systems through compartments: EI 60 vertically, compartment value horizontally, distance to combustibles, fill-in
Flue systems running vertically through several compartments have EI 60 of heat-resistant RF1 outside the installation room or sit in such a fire protection element, in single-family houses and flats EI 30; horizontally the fire resistance of the compartment applies.
-
VKF-24-15-016
Explosion flaps, flue fans and cleaning openings
For fuels prone to deflagration, such as fine-grained coal or wood chips, explosion flaps belong in the flue system, in the boiler room close to the connecting pipe entry and at least the cross-section of the flue. Flue fans create positive pressure only if the system is approved for it.
-
VKF-24-15-017
Solid fuels: daily consumption in the installation room, store EI 60, at most 10 m³ in the boiler room
Only a day's consumption may be stored in the installation room, shielded from the unit; larger quantities go into other rooms or outdoors. In single-family houses wood or coal up to 5 m³ is allowed in rooms of any construction.