Rule Fire protection directive 24-15 Heating plant

Flue systems: connections, continuous routing and minimum height above roof

VKF-24-15-014 pragmaticBIM.ch/vkf-24-15-014

Only units that in normal operation do not produce flue gases hotter than the system allows are connected; connecting pipes enter in the same storey and fire compartment.

Description

Common flues under negative pressure are allowed for up to four connections and 70 kW total output; units above 70 kW, open fireplaces and positive-pressure units need separate flues. Flues run continuously, if possible vertically, above the roof: 1 m for discharge in the roof surface, 0.5 m at the ridge or on non-accessible flat roofs, 2 m on accessible flat roofs; with less than 3 m distance to higher building parts, up above them. Not yet checkable: the model holds no flue system with classification, routing, minimum height above roof and clearance.

Source

VKF-Brandschutzrichtlinie 24-15 Wärmetechnische Anlagen (2015) (p. 11)