Rule Fire protection directive 24-15 Heating plant

Clearances to combustibles: 0.1 / 0.2 / 0.4 m by surface temperature, 0.8 m and 2 m for radiation

VKF-24-15-010 pragmaticBIM.ch/vkf-24-15-010

Adequate clearances apply to all combustible materials, as given in the declaration of performance or VKF technical information, otherwise 0.1 m for surface temperatures up to 100 °C, 0.2 m up to 200 °C and 0.4 m up to 400 °C.

Description

For open or glazed fireboxes 0.8 m applies in the radiation zone, and 2 m for directed heat radiation. The distances also apply to RF1 that is not heat-resistant or thinner than 60 mm; with a back-ventilated radiation shield, fire protection board or 60 mm thick wall they may be halved. Not yet checkable: the model does not show surface temperature, combustibility of surroundings and clearances.

Source

VKF-Brandschutzrichtlinie 24-15 Wärmetechnische Anlagen (2015) (p. 8)