Rule Fire protection directive 24-15 Heating plant
Base plate, floor protection and wall behind firing units in heat-resistant RF1
VKF-24-15-009
pragmaticBIM.ch/vkf-24-15-009
On combustible floor constructions firing units stand on a base plate of heat-resistant RF1, individually made units such as tiled stoves on a 0.12 m thick slab of stone, concrete or equivalent. In front of solid-fuel units lies a heat-resistant RF1 floor covering extending 0.4 m in front of the loading opening.
Description
Walls behind are made of heat-resistant RF1 over the full room height and 0.2 m beyond the unit at the sides; walls adjoining individually made units are 0.12 m thick. Not yet checkable: the model does not show surface temperature, combustibility of surroundings and clearances.
Source
VKF-Brandschutzrichtlinie 24-15 Wärmetechnische Anlagen (2015) (p. 7)
More rules for Fire protection directive 24-15 Heating plant
-
VKF-24-15-010
Clearances to combustibles: 0.1 / 0.2 / 0.4 m by surface temperature, 0.8 m and 2 m for radiation
Adequate clearances apply to all combustible materials, as given in the declaration of performance or VKF technical information, otherwise 0.1 m for surface temperatures up to 100 °C, 0.2 m up to 200 °C and 0.4 m up to 400 °C.
-
VKF-24-15-011
Fireplaces, tiled stoves, pellet firing units, commercial kitchens and cookers
For fireplaces the information of the declaration of performance or VKF technical information applies. Tiled and storage stoves keep 0.2 m at the sides, back and top and 0.5 m at the firing opening from combustibles and have cleaning openings.
-
VKF-24-15-012
Mobile firing units and small appliances: clearance, combustion air, no continuous heating without flue
Mobile firing units such as building dryers or air heaters keep as much distance from combustibles as comparable stationary units, need sufficient combustion air and, without direct flue routing, stand only in open halls, shells or well-ventilated rooms, not openly in rooms with large occupancy.