Rule Fire protection directive 24-15 Heating plant

Base plate, floor protection and wall behind firing units in heat-resistant RF1

VKF-24-15-009 pragmaticBIM.ch/vkf-24-15-009

On combustible floor constructions firing units stand on a base plate of heat-resistant RF1, individually made units such as tiled stoves on a 0.12 m thick slab of stone, concrete or equivalent. In front of solid-fuel units lies a heat-resistant RF1 floor covering extending 0.4 m in front of the loading opening.

Description

Walls behind are made of heat-resistant RF1 over the full room height and 0.2 m beyond the unit at the sides; walls adjoining individually made units are 0.12 m thick. Not yet checkable: the model does not show surface temperature, combustibility of surroundings and clearances.

Source

VKF-Brandschutzrichtlinie 24-15 Wärmetechnische Anlagen (2015) (p. 7)

More rules for Fire protection directive 24-15 Heating plant

Contact

abstract ag

Imprint · Picassoplatz 4, 4052 Basel