Rule Fire protection directive 24-15 Heating plant
Single-family houses and flats: solid-fuel firing units in a room with EI 30
VKF-24-15-003
pragmaticBIM.ch/vkf-24-15-003
For liquid and gaseous fuels the construction and finish of the installation room are unrestricted.
Description
Solid-fuel units that also heat the room may stand in permanently used rooms such as kitchen or living room; otherwise they need a room with the fire resistance of the use-related compartmentation, at least EI 30, with EI 30 doors. With low fire risk the installation room may also serve other purposes. Not yet checkable: the model does not show nominal heat output, fuel, type of installation and fire resistance of the boiler room.
Source
VKF-Brandschutzrichtlinie 24-15 Wärmetechnische Anlagen (2015) (p. 6)
More rules for Fire protection directive 24-15 Heating plant
-
VKF-24-15-004
Boiler room in buildings with several compartments: EI 30 up to 70 kW, EI 60 above, doors EI 30
Firing units stand in separate boiler rooms. Their fire resistance depends on the total nominal heat output: up to 70 kW the use-related compartment value, at least EI 30; above that at least EI 60.
-
VKF-24-15-005
Boiler room with direct access from outdoors: above 1,200 kW on ground floor or lower, above 600 kW from 2nd basement
Boiler rooms on the ground floor or lower for plants above 1,200 kW nominal heat output, and boiler rooms on the second basement or lower for plants above 600 kW, get direct access from outdoors.
-
VKF-24-15-006
Open installation in single-storey halls and commercial buildings with low fire load
In single-storey halls and multi-storey industrial and commercial buildings with use-related compartments, firing units of any output may stand openly if operation requires it, the clearances are kept and the fire load in the room is low.