Rule Fire protection directive 21-15 Smoke and heat exhaust systems
Power supply for safety purposes independent of the general supply
VKF-21-15-014
pragmaticBIM.ch/vkf-21-15-014
Smoke and heat exhaust systems and smoke-protection pressurization systems are connected to suitable power sources that are independent of the general power supply. Not yet checkable: the model holds no trigger and control points of the system and no power source for safety purposes.
Source
VKF-Brandschutzrichtlinie 21-15 Rauch- und Wärmeabzugsanlagen (2015) (p. 10)
More rules for Fire protection directive 21-15 Smoke and heat exhaust systems
-
VKF-21-15-015
Use of ventilation systems for smoke extraction only if RWA requirements are met
Ventilation and air-conditioning systems may be used for smoke and heat extraction only if the affected plant parts meet the requirements for smoke and heat exhaust systems. Not yet checkable: the model holds no smoke and heat exhaust system and no assignment of one to fire compartments.
-
VKF-21-15-016
Concepts: fire-brigade fans down to the 1st basement, natural systems not below ground, extraction under the ceiling
Smoke clearance with fire-brigade fans assumes response forces on site within 15 minutes of the alarm, needs inlet openings for setting up the fans in addition to the exhaust openings, and below ground is permitted only down to the 1st basement unless supply air comes from outdoors on the same level.
-
VKF-21-15-017
Project review, acceptance, periodic inspection and maintenance
On request of the fire protection authority, projects are submitted for approval in good time. Systems with performance proof are accepted after an installation certificate exists, as are extensions and substantial changes.