Rule Fire protection directive 20-15 Fire alarm systems
Fire-brigade control and indicating unit at a safe, easily accessible location
VKF-20-15-007
pragmaticBIM.ch/vkf-20-15-007
Fire-brigade control and indicating units of systems with more than one detector zone stand at a safe location that is easily accessible for the fire brigade, in the escape route or at the fire-brigade access. The operating-state indication is in the immediate vicinity, and unobstructed access is ensured.
Description
Not yet checkable: the model holds no fire alarm control panel, no fire-brigade control unit and no fire-mode control as a system.
Source
VKF-Brandschutzrichtlinie 20-15 Brandmeldeanlagen (2015) (p. 6)
More rules for Fire protection directive 20-15 Fire alarm systems
-
VKF-20-15-008
Alerting: internal and external alarm, delays of at most 3 and 5 minutes
Every response triggers an internal and an external alarm; the external one goes directly to the public fire alarm receiving point. Switch-offs and faults are signalled visually and audibly and forwarded to a permanently staffed point.
-
VKF-20-15-009
Fire-mode controls: activation of fire protection equipment, documented and tested
The fire alarm system can trigger fire doors and shutters, smoke and heat exhaust systems, transport systems and ventilation systems. For selective fire-mode controls the trigger is as a rule not by manual call points, which is considered in the fire protection concept.
-
VKF-20-15-010
Fire alarm control panel: safe location, monitored compartment, several panels in a room with EI 30
Fire alarm control panels and remote indicating panels stand at a safe, easily accessible location; the fire compartment of the panel is monitored.