Rule Fire protection directive 20-15 Fire alarm systems
Alerting: internal and external alarm, delays of at most 3 and 5 minutes
VKF-20-15-008
pragmaticBIM.ch/vkf-20-15-008
Every response triggers an internal and an external alarm; the external one goes directly to the public fire alarm receiving point. Switch-offs and faults are signalled visually and audibly and forwarded to a permanently staffed point.
Description
A presence or investigation delay is allowed only while an alarm organisation with at least two instructed persons is present, at most 3 minutes (presence) or 5 minutes (investigation), can only be activated manually and is reset automatically at least daily. Not yet checkable: the model holds no fire alarm control panel, no fire-brigade control unit and no fire-mode control as a system.
Source
VKF-Brandschutzrichtlinie 20-15 Brandmeldeanlagen (2015) (p. 7)
More rules for Fire protection directive 20-15 Fire alarm systems
-
VKF-20-15-009
Fire-mode controls: activation of fire protection equipment, documented and tested
The fire alarm system can trigger fire doors and shutters, smoke and heat exhaust systems, transport systems and ventilation systems. For selective fire-mode controls the trigger is as a rule not by manual call points, which is considered in the fire protection concept.
-
VKF-20-15-010
Fire alarm control panel: safe location, monitored compartment, several panels in a room with EI 30
Fire alarm control panels and remote indicating panels stand at a safe, easily accessible location; the fire compartment of the panel is monitored.
-
VKF-20-15-011
Detector zones: fire location clearly identifiable, vertical shafts combined
The entire monitored area is divided into detector zones so that the fire location is shown quickly and unambiguously. Vertical escape routes, light, lift and installation shafts and tower-like structures form one common detector zone.