Rule Fire protection directive 20-15 Fire alarm systems

Alerting: internal and external alarm, delays of at most 3 and 5 minutes

VKF-20-15-008 pragmaticBIM.ch/vkf-20-15-008

Every response triggers an internal and an external alarm; the external one goes directly to the public fire alarm receiving point. Switch-offs and faults are signalled visually and audibly and forwarded to a permanently staffed point.

Description

A presence or investigation delay is allowed only while an alarm organisation with at least two instructed persons is present, at most 3 minutes (presence) or 5 minutes (investigation), can only be activated manually and is reset automatically at least daily. Not yet checkable: the model holds no fire alarm control panel, no fire-brigade control unit and no fire-mode control as a system.

Source

VKF-Brandschutzrichtlinie 20-15 Brandmeldeanlagen (2015) (p. 7)