Rule Fire protection directive 20-15 Fire alarm systems
Fire-mode controls: activation of fire protection equipment, documented and tested
VKF-20-15-009
pragmaticBIM.ch/vkf-20-15-009
The fire alarm system can trigger fire doors and shutters, smoke and heat exhaust systems, transport systems and ventilation systems. For selective fire-mode controls the trigger is as a rule not by manual call points, which is considered in the fire protection concept.
Description
Fire-mode controls are documented and tested. Not yet checkable: the model holds no fire alarm control panel, no fire-brigade control unit and no fire-mode control as a system.
Source
VKF-Brandschutzrichtlinie 20-15 Brandmeldeanlagen (2015) (p. 7)
More rules for Fire protection directive 20-15 Fire alarm systems
-
VKF-20-15-010
Fire alarm control panel: safe location, monitored compartment, several panels in a room with EI 30
Fire alarm control panels and remote indicating panels stand at a safe, easily accessible location; the fire compartment of the panel is monitored.
-
VKF-20-15-011
Detector zones: fire location clearly identifiable, vertical shafts combined
The entire monitored area is divided into detector zones so that the fire location is shown quickly and unambiguously. Vertical escape routes, light, lift and installation shafts and tower-like structures form one common detector zone.
-
VKF-20-15-012
Manual call points in escape routes and hazardous areas, clearly visible, mounting height about 1.5 m
Manual call points are fitted clearly visibly in escape routes, for example at exits, passages, vertical escape routes and extinguishers, and in particularly hazardous areas.