Rule Fire protection directive 20-15 Fire alarm systems

Areas that may be exempted from monitoring

VKF-20-15-006 pragmaticBIM.ch/vkf-20-15-006

Exemptions are possible, among others, for installation shafts that are inaccessible or free of ignition hazards, wet rooms without combustible stock, lift shafts with a separate machine room, residential areas separated as a fire compartment, cold rooms up to 50, 200 or 600 m² depending on insulation and...

Description

Exemptions are possible, among others, for installation shafts that are inaccessible or free of ignition hazards, wet rooms without combustible stock, lift shafts with a separate machine room, residential areas separated as a fire compartment, cold rooms up to 50, 200 or 600 m² depending on insulation and separation, oil tank rooms EI 60 up to 150 m², areas under galleries up to 3 m wide or 30 m², and voids above suspended ceilings and below raised floors with low fire load or low height (below 0.15 m or 0.2 m). Not yet checkable: the model does not give installation shafts, voids, fire load and cold rooms the necessary characteristic values.

Source

VKF-Brandschutzrichtlinie 20-15 Brandmeldeanlagen (2015) (p. 6)