Rule Fire protection directive 17-15 Escape route marking, safety lighting, safety power supply
Safety lighting in escape routes: at least 1 lux
VKF-17-15-011
pragmaticBIM.ch/vkf-17-15-011
The illuminance of safety lighting in escape routes is at least 1 lux. Not yet checkable: the model carries no illuminance for luminaires or escape routes.
Source
VKF-Brandschutzrichtlinie 17-15 Kennzeichnung von Fluchtwegen, Sicherheitsbeleuchtung, Sicherheitsstromversorgung (2015) (p. 6)
More rules for Fire protection directive 17-15 Escape route marking, safety lighting, safety power supply
-
VKF-17-15-012
Power sources for safety purposes: independent of the normal supply
A power supply for safety purposes is needed for the safety lighting of rooms, escape routes and escape signs, and for fire protection installations such as sprinkler pumps and fire-brigade lifts.
-
VKF-17-15-013
Safety power sources: installation room at least EI 30, separation EI 60
Power sources for safety purposes and their controls are installed in fixed positions in rooms with a low fire risk. The installation room matches the fire resistance of the structure or the fire compartments, but at least EI 30; the doors are EI 30.
-
VKF-17-15-014
Distribution network for safety purposes: separate circuits, functional endurance, separation
Circuits for safety purposes are laid independently of other circuits. The distribution network is protected against fire so that functional endurance matches the intended operating time of the connected consumers.